home *** CD-ROM | disk | FTP | other *** search
/ Spec Disk 1998 Spring 4.0 / Spec Disk 1998 Spring 4.0.iso / generic / 15815met.gen < prev    next >
Text File  |  1998-06-10  |  9KB  |  205 lines

  1.     SECTION 15815
  2.  
  3.     FLEXIBLE DUCTWORK
  4. NOTE ** This section is based on flexible metal duct units produced by:
  5. NOTE ** 
  6. NOTE **    METALFLEX Division, Professional Duct Systems, Inc.
  7. NOTE **    6180 Boat Rock Boulevard, S. W.
  8. NOTE **    Atlanta, GA  30336
  9. NOTE **    Tel:  (888) MTL-FLEX (888-685-3539)
  10. NOTE ** 
  11. NOTE ** Products include UL-listed non-insulated and insulated flexible aluminum duct, and non-listed acoustical insulated duct.  METALFLEX UL-listed duct is approved for use under numerous building codes.
  12. NOTE ** 
  13. NOTE ** SECTION 15815 - FLEXIBLE DUCTWORK, Copyright 1997, The Architect's Catalog, Inc.
  14.  
  15. PART 1    GENERAL
  16.  
  17. 1.1    SECTION INCLUDES
  18. NOTE ** Delete items below not required for project.
  19.  
  20.     A.    Non-Insulated Flexible Duct.
  21.  
  22.     B.    Insulated Flexible Duct.
  23.  
  24.     C.    Acoustical Insulated Flexible Duct.
  25.  
  26. 1.2    RELATED SECTIONS
  27. NOTE ** Delete any sections below not relevant to this project; add others as required.
  28.  
  29.     A.    Section 15810 - Ducts.
  30.  
  31.     B.    Section 15822 - Sound Attenuators.
  32.  
  33. 1.3    REFERENCES
  34. NOTE ** Delete references from the list below that are not actually required by the text of the edited section.
  35.  
  36.     A.    ASTM C 518 - Standard Test Method for Steady-State Heat Flux Measurements and Thermal Transmission Properties by Means of the Heat Flow Apparatus.
  37.  
  38.     B.    ASTM E 84 - Standard Test Method for Surface Burning Characteristics of Building Materials.
  39.  
  40.     C.    ASTM E 96 - Standard Test Methods for Water Vapor Transmission of Materials.
  41.  
  42.     D.    NFPA 90A - Standard for Installation of Air Conditioning and Ventilating Systems; National Fire Protection Association.
  43.  
  44.     E.    NFPA 90B - Standard for Installation of Warm Air Heating and Air Conditioning Systems; National Fire Protection Association.
  45.  
  46.     F.    UL 181 - Standard for Factory Made Air Ducts and Air Connectors; Underwriters Laboratory.
  47.  
  48. 1.4    SUBMITTALS
  49.  
  50.     A.    Submit under provisions of Section 01300.
  51.  
  52.     B.    Product Data:  Manufacturer's product literature for each type unit.
  53. NOTE ** Delete paragraph below if building code not cited in referenced Article.
  54.  
  55.     C.    Quality Assurance Submittals:  Certified test reports from independent testing laboratory supporting compliance of products to Building Code cited in QUALITY ASSURANCE Article of this Section.
  56. NOTE ** Delete Article below if only acoustical insulated duct units  specified.
  57.  
  58. 1.5    QUALITY ASSURANCE
  59.  
  60.     A.    Regulatory requirements:  UL compliance; affix UL Listing Mark, with Class code, to each UL listed unit.
  61. NOTE ** Edit subparagraph below for applicable jurisdiction; delete subparagraph if not applicable.
  62.  
  63.         B.    Code compliance:  Units listed as complying with the following:
  64.             1.    SBCC.
  65.             2.    ICBO.
  66.             3.    BOCA.
  67.             4.    HUD 515-2.1(b).
  68.             5.    City of Chicago, IL.
  69.             6.    New York, NY.
  70.             7.    San Francisco, CA.
  71.             8.    Dade County, FL Building Code.
  72.  
  73. PART 2    PRODUCTS
  74.  
  75. 2.1    MANUFACTURERS
  76.  
  77.     A.    Acceptable Manufacturer:  METALFLEX Division of Professional Duct Systems, Inc., 6180 Boat Rock Blvd., S.W., Atlanta, GA  30336. ASD. Tel: (888) MTL-FLEX (888-685-3539).
  78. NOTE ** Delete one of the two following paragraphs; coordinate with Division 01 requirements.
  79.  
  80.     B.    Requests for substitutions will be considered in accordance with provisions of Section 01600.
  81.  
  82.     C.    Substitutions:  Not permitted.
  83.  
  84.     D.    Supply all products specified in this section from a single manufacturer.
  85.  
  86. 2.2    NON-INSULATED FLEXIBLE AIR DUCT
  87.  
  88.     A.    Acceptable Product:  METALFLEX V-100-UL.
  89. NOTE ** Select product V-100-UL for compressed duct; select product V-100-S-UL for non-compressed duct.
  90.  
  91.     B.    Acceptable Product:  METALFLEX V-100-S-UL.
  92.  
  93.     C.    Materials:  Aluminum, formed into corrugated circular duct in eight foot length with watertight seams and continuous lock seam connection at each end.
  94.  
  95.     D.    Characteristics:
  96.         1.    Meet requirements of UL 181.
  97.         2.    Listed Class 0 Air Duct in accordance with NFPA 90A and NFPA 90B.
  98.         3.    Fire Hazard Classification in accordance with ASTM E 84:
  99.             a.    Flame Spread:  Not exceeding 0.
  100.             b.    Smoke Developed:  Not exceeding 0.
  101.         4.    Maximum velocity air handling capability:  5000 feet per minute.
  102.         5.    Maximum operating pressure, positive and negative:
  103.             a.    Duct diameter 3 inches to 10 inches:  Plus or minus 12 inches WG.
  104.             b.    Duct diameter 12 inches to 24 inches:  Plus or minus 8 inches WG.
  105.             c.    Operating temperature range:  Minus 100 degrees F to plus 430 degrees F.
  106. NOTE ** Retain sentence below if specifying product V-100-UL.
  107.  
  108.         6.    Ship duct lengths compressed to 2 feet, 8 inch length.
  109.  
  110.     E.    Accessories:  Furnish each length with universal male/female connector at each end.
  111. NOTE ** Paragraph above specifies standard accessories for product V-100-UL (compressed duct); paragraph below specifies standard accessories for product V-100-S-UL (non-compressed duct).
  112.  
  113.     F.    Accessories:  Furnish each length with male/female connector one end.
  114.  
  115. 2.3    INSULATED FLEXIBLE AIR DUCT
  116. NOTE ** The V-200 product line has gray polyethylene vapor barrier.  Select product V-200-UL for compressed duct; select product V-200-S-UL for non-compressed duct.
  117.  
  118.     A.    Acceptable Product:  METALFLEX V-200-UL.
  119.  
  120.     B.    Acceptable Product:  METALFLEX V-200-S-UL.
  121. NOTE ** The V-250 product line has metalized film vapor barrier having greater moisture resistance than the V-200 product line.  Select product V-250-UL for compressed duct; select product V-250-S-UL for non-compressed duct.
  122.  
  123.     C.    Acceptable Product:  METALFLEX V-250-UL.
  124.  
  125.     D.    Acceptable Product:  METALFLEX V-250-S-UL.
  126.  
  127.     E.    Materials:
  128.         1.    Inner Duct Core:  Aluminum, formed into corrugated circular duct in eight foot length with watertight seams and continuous lock seam connection at each end.
  129. NOTE ** Standard insulating layer thickness is 1-1/2 inches; edit below if higher 'R' value is required.
  130.  
  131.         2.    Insulating Layer:  Non-combustible, 1-1/2 inches thickness.
  132. NOTE ** The V-200 product line has gray polyethylene vapor barrier; the V-250 product line has metalized film vapor barrier.
  133.  
  134.         3.    Vapor Barrier:  Polyethylene, gray color, having 0.10 Perm rating in accordance with ASTM E 96, Procedure A.
  135.         4.    Vapor Barrier:  Metalized film, having 0.05 Perm rating in accordance with ASTM E 96, Procedure A.
  136.  
  137.     F.    Characteristics:
  138.         1.    Meet requirements of UL 181.
  139.         2.    Listed Class 1 Air Duct in accordance with NFPA 90A and NFPA 90B.
  140.         3.    Fire Hazard Classification in accordance with ASTM E 84:
  141.             a.    Flame Spread:  Not exceeding 25.
  142.             b.    Smoke Developed:  Not exceeding 50.
  143.         4.    Maximum velocity air handling capability:  5000 feet per minute.
  144.         5.    Maximum operating pressure, positive and negative:
  145.             a.    Duct diameter 4 inches to 10 inches:  Plus or minus 12 inches WG.
  146.             b.    Duct diameter 12 inches to 20 inches:  Plus or minus 8 inches WG.
  147.         6.    Operating temperature range:  Minus 20 degrees F to 250 degrees F.
  148. NOTE ** Ratings specified below are standard; edit if higher thermal  efficiency required.
  149.  
  150.         7.    Thermal efficiency:
  151.             a.    C-factor, calculated at 75 degrees F mean:  0.173.
  152.             b.    R-Value, calculated by ADC FD72-R1 method:  5.79 average.
  153.             c.    R-Value, calculated by ASTM C 518 method:  4.2 average.
  154. NOTE ** Retain sentence below if specifying product V-200-UL or V-250-UL.
  155.  
  156.         8.    Ship duct lengths compressed to 2 feet, 8 inch length.
  157.  
  158.     G.    Accessories:  Furnish each length with universal male/female connector at each end.
  159. NOTE ** Paragraph above specifies standard accessories for products V-200-UL and V-250-UL (compressed duct); paragraph below specifies standard accessories for products V-200-S-UL and V-250-S-UL (non-compressed duct).
  160.  
  161.     H.    Accessories:  Furnish each length with male/female connector one end.
  162.  
  163. 2.4    ACOUSTICAL INSULATED FLEXIBLE AIR DUCT
  164. NOTE ** Product V-450-S-DB has metalized film vapor barrier with high moisture resistance. The product is non-compressed duct.
  165.  
  166.     A.    Acceptable Product:  METALFLEX V-450-S-DB.
  167.  
  168.     B.    Materials:
  169.         1.    Inner Duct Core:  Aluminum, formed into corrugated circular duct in eight foot length with watertight seams and continuous lock seam connection at each end.
  170.         2.    Insulating Layer:  Non-combustible, 1-1/2 inches thickness.
  171.         3.    Vapor Barrier:  Metalized film, having 0.05 Perm rating in accordance with ASTM E 96, Procedure A.
  172.  
  173.     C.    Characteristics:
  174.         1.    Maximum velocity air handling capability:  2500 feet per minute.
  175.         2.    Maximum operating pressure, positive and negative, for duct diameter 4 inches to 20 inches:  Plus or minus 2 inches WG.
  176.         3.    Operating temperature range:  Minus 20 degrees F to plus 250 degrees F.
  177.         4.    Thermal efficiency:
  178.             a.    C-factor, calculated at 75 degrees F mean:  0.173.
  179.             b.    R-Value, calculated by ADC FD72-R1 method:  5.79 average.
  180.             c.    R-Value, calculated by ASTM C 518 method:  4.2 average.
  181.  
  182.     D.    Accessories:  Furnish each length with male/female connector one end.
  183.  
  184. PART 3    EXECUTION
  185.  
  186. 3.1    INSTALLATION
  187. NOTE ** Verify specification section reference below.  Edit if required.
  188.  
  189.     A.    Install flexible ductwork in accordance with provisions of Section 15810 - Ducts.
  190.  
  191.     END OF SECTION
  192. ??
  193.  
  194.  
  195.  
  196.  
  197.  
  198.  
  199.  
  200.  
  201.  
  202.     15815-1